Displaying report 1-1 of 1.
Reports until 19:24, Tuesday 25 February 2014
H1 ISC (CDS)
jameson.rollins@LIGO.ORG - posted 19:24, Tuesday 25 February 2014 (10332)
main LSC library part input (PD/DOF) matrix updated to use new cdsRampMux

The cdsRampMuxMatrix part, which is new to RCG 2.8 (and updated in 2.8.3), allows for pre-writing a new matrix and then loading it with a specified ramp time from the current values to the new ones.

This part has been swaped into the PD_DOF_MTRX position in the main LSC library part in:

USERAPPS/lsc/common/models/lsc.mdl

The h1lsc model was rebuild/installed/restarted, and has been tested and seems to be working as expected.

The channel interface to the matrix has now changed.  The readback channel retains the same form as the non-ramping matrix, but new channels are added to write the new matrix:

LSC-PD_DOF_MTRX__ current setting readback
LSC-PD_DOF_MTRX_SETTING__ new setting value
LSC-PD_DOF_MTRX_RAMPING__ indicator that element is ramping
LSC-PD_DOF_MTRX_TRAMP ramp time
LSC-PD_DOF_MTRX_LOAD_MATRIX load new values

Scripts/guardian will need to be modified to write new matrix values accordingly.

The MEDM screens for the input matrix were updated with a new interface for the matrix.  The updates screens are (screenshots below):

USERAPPS/lsc/common/medm/LSC_CUST_PD_DOF_MTRX_VAC.adl
  USERAPPS/lsc/common/medm/LSC_CUST_PD_DOF_MTRX_AIR1F.adl
  USERAPPS/lsc/common/medm/LSC_CUST_PD_DOF_MTRX_AIR2F.adl
  USERAPPS/lsc/common/medm/LSC_CUST_PD_DOF_MTRX_CM.adl

Each matrix element is split vertically, with the readback of the current value at the top, and the new value at the bottom.  The boxes are colored to indicate the state:

The "Kissel buttons" on the main LSC_OVERVIEW screen did not have to be modified since the readback channel did not change.