I have been checking the status of the front end systems while h1boot was down between 17:13 ad 17:45UTC today.
	- 
		all front end models continued to run
 
	- 
		the epics sequencer froze up (trying to checksum the configuration files) meaning that no data was being transferred between the EPICS databases and the front end code
 
	- 
		On MEDM screens: monitor channels froze at their last value, control channels permitted changes which were then not applied to the model
 
	- 
		DAQ data (fast and slow) continued to flow from the front end models to the DAQ
 
	- 
		all models' CPU usage improved slightly, either speeding up by a microsecond or becoming less noisy, as EPICS data was not being transferred to the front end core.
 
	as a consequence to this, CONLOG was recording changes which may not have been applied, and GUARDIAN was running on unchanging input data.