Reports until 15:15, Tuesday 13 May 2014
H1 SEI (SEI, SUS)
sheila.dwyer@LIGO.ORG - posted 15:15, Tuesday 13 May 2014 (11858)
ETMY trip, more recovery from maintenence

ETMY ISI tripped again, possibly when I isolated HEPI after already isolating the ISI.  The blends were also set incorrectly. (all Tbetter) We have been using Tcrayy for RZ on stage 1 and 2, and I think that we are still using Tcrappy for stage 2 RX (I wrote that Tbetter was wrong in alog 11563, and I'm not aware if anyone has fixed it.)

I also noticed that it is possible for the TMS guardian to say that TMS is alinged, even when the master switch is off.

I also burted asc and lsc to mid night last night.

I also moved IMTY blends from T750 back to Tcrappy, and turned on sensor correction