patrick.thomas@LIGO.ORG - posted 10:27, Tuesday 20 May 2014 (11984)
dust monitor code updated to 1.3.0
This completes WP 4633.

This was done to communicate with the MetOne model 6000 installed in the H1 PSL diode room.

The h0dustdr, h0dustex, h0dustey, h0dustlab, h0dustlvea, h0dustmx and h0dustmy target directories in /ligo/lho/h0/target were copied to /ligo/lho/h0/target_archive and updated. The h0dustex, h0dustey, h0dustlvea and h0dustlab IOCs were restarted and burtrestored to the snapshot files in /ligo/cds/lho/h0/burt/2014/05/19/08:00.

The h0dustdr IOC was started. The settings were changed to:
Sample Time: 20 seconds
Hold Time: 300 seconds
0.3 micron minor alarm: 100
0.3 micron major alarm: 200
0.5 micron minor alarm: 100
0.5 micron major alarm: 200