Reports until 14:43, Wednesday 28 May 2014
H1 ISC
sheila.dwyer@LIGO.ORG - posted 14:43, Wednesday 28 May 2014 - last comment - 15:42, Tuesday 10 March 2015(12120)
Whitening not switching and solution

The corner whitening filters were not switching, with an error message invalid data chn and readback different for Refl 9 and refl air 9, and for POP we had an error message invalid data for channels 1, 2, 3 and 4. 

Daneil fixed this by going to the system manager for the corner, finding the X gateway under device 1, corner MSR L0, Corner MSR L8_9 Vertex, going to the Online tab, and clicking on several of the buttons under state machine (Init, pre-op, safe op, op) in an order that seemed random to me. 

I am just writing down the solution to this problem so that we can look it up next time it happens.

Comments related to this report
sheila.dwyer@LIGO.ORG - 15:42, Tuesday 10 March 2015 (17178)

This happened again, we repeated what we did, on the Corner Chassis 2 L-2 (X-gateway) under Online the current state was safeop.  We hit a bunch of buttons (including clear error) until it arrived in OP.  We repeated this for L-1, which was also in safe OP.  

An alternative solution would be to restart h1ecatc1