H1 CDS (SUS)
david.barker@LIGO.ORG - posted 16:16, Thursday 19 June 2014 (12427)
HWWD tests at EY

Jim and Dave.

We revisted the problem of not being able to control the HWWD unit when it is installed at EY, but the same unit works at other locations. We had tried the 4th DB-9 connector of the binary out chassis for both ETMY and TMSY. On the ETMY chassis all ports are used except the 4th, on the TMSY chassis only the first two ports are used. This afternoon we moved the binary out cable to the 3rd port of the TMSY chassis, and it works. We would like to connect the HWWD to the primary model (ETMY), so it would be good to verify the 4th port has a problem.

To perform this test, I modifed the SUS model h1sustmsy and compiled against RCG-branch2.8. The HWWD and SWWD systems are now ready for combined shake tests next week.