Following the DACKILL naming decision yesterday, I installed the latest SWWD version of the IOP models at both end stations. The new models are: h1iopsusex, h1iopsusey, h1iopseiex and h1iopseiey. All user models were restarted as part of this install. The h1iopsusey model has test oscillators which sum with the SIDE OSEM signal. I was able to use the oscillator to test the SUS-to-SEI trip and verify SEI DACs are killed after 10 minute have elapsed. At EY I tested the system by PANIC crashing SUS which started the SEI countdown.

Comments related to this report
david.barker@LIGO.ORG - 17:08, Thursday 26 June 2014 (12505)DAQ

To support the HWWD and SWWD install/tests the DAQ was restarted. Note, the corner station IOP models were make/make-installed but not restarted today, which is why their DAQ status is now 0x2000. This will be remedied when these models are restarted at a later date.