In this directory: /opt/rtcds/lho/h2/target/h2isiitmy/h2isiitmyepics/db/H2
There is a file: h2isiitmy1.db
That contains a field: grecord(ai,"H2:ISI-ITMY_ST2_PAYLOADWD_IN")
To make a watchdog link, we turned it into a calc field
grecord(calc,"H2:ISI-ITMY_ST2_PAYLOADWD_IN")
{
field(PREC,"3")
field(SCAN, "0.1 second")
field(INPA, "H2:SUS-ITMY_M0R0_WDMON_STATE NPP NMS")
field(CALC, "A")
}
Then we restarted the Front end. EVERYTIME YOU REBUILD THE FRONT END YOU HAVE TO EDIT THE FILE.
Note that the mapping to the BSCWATCHDOG c-code, medm, and simulink don't agree. But I leave this to SEIsters to fix.
When the Quad trips the lights behind the ACT limit on the ISI watchdog go red.
Note - because this is hardwired, there is no bypass so the QUAD watchdog MUST be green.
s