Summary of recent rash of CDS problems

Jim, Dave

With so much going on this weekend and today, I thought it would be nice to provide a top level summary of events.

The LDAS raid issue is thought to be completely unrelated to the various FE issues, and was purely coincidental.

There is no obvious connection between the various FE issues, but we cannot imaging they are coincidental.

All times are PDT.

LDAS disk9 failure in RAID

Fri 8/8 21:57 Warning message disk9
Fri 8/8 22:37 Error Disk9, continuous
Sat 8/9 01:52 h1fw0 single restart
Sat 8/9 04:02 h1fw0 regularly restarting
Sat 8/9 15:57 problem resolved, disk9 removed from raid

h1sush2a CPU freeze

Sat 8/9 00:06 cpu freeze, DAQ data bad for many other FE
Sat 8/9 11:48 pwr CPU, large IRIGB error on IOP
Sat 8/9 11:54 restart IOP, still large IRIGB errors
Sat 8/9 12:11 pwr CPU and IOChassis, all is good

h1seib1 CPU freeze

Sun 8/10 18:46 cpu freeze, DAQ data on others good
Mon 8/11 08:35 pwr cpu , IRIGB drifted bad
Mon 8/11 08:39 IRIGB drifted good, all is good

h1susb123 CPU freeze

Mon 8/11 13:46 cpu freeze, DAQ data good on other FE. SWWD causes SEI trip 5 mins later
Mon 8/11 13:58 pwr cpu. All looks good but DAC is undrivable (discovered later)
Mon 8/11 14:34 DAC problem discovered, fixed with restart of IOP

h1seih23 DACs not driving

Sat 8/9 15:30 h1seih23 DACs not being driven
Mon 8/11 10:42 fixed by restarting IOP
Comments related to this report
david.barker@LIGO.ORG - 16:58, Monday 11 August 2014 (13342)CDS

here are the console images for the three cpu freeze up events (h1sush2b, h1seib1, h1susb123)

Images attached to this comment