Reports until 13:32, Tuesday 09 September 2014
H1 CDS (ISC)
david.barker@LIGO.ORG - posted 13:32, Tuesday 09 September 2014 (13835)
h1lsc downgraded to RCG2.8.3 to correct h1lsc DAQ data

An RCG problem with 2.8.4 and later for models using the ramped mux matrix resulted in some of h1lsc's slow channels being channel shifted in the DAQ. This only affects 16Hz slow channels, fast data is stored correctly.

The build release pointer were changed from 2.8.5 to 2.8.3, the h1lsc model was recompiled and installed, the pointers were then reset back to 2.8.5.

h1lsc model was restarted. Due to a change with its INI file, the DAQ was also restarted.

We verified the slow data is  being stored correctly.