Reports until 13:12, Tuesday 28 October 2014
H1 CDS
patrick.thomas@LIGO.ORG - posted 13:12, Tuesday 28 October 2014 - last comment - 13:57, Tuesday 28 October 2014(14674)
more Beckhoff work
Work under permit 4919 and possible missed stuff from 4917:

corner station

quit IOC
C:/SlowControls: svn update
H1ECATC1: PLC3: 'Update from source'
C:/SlowControls/Target/H1ECATC1/H1ECATC1.tsm: PLC1 rescan project, PLC3 rescan project; Actions -> Generate mappings, Check configuration; Save
Copy C:/SlowControls/Target/H1ECATC1/H1ECATC1.tsm to C:/SlowControls/Scripts/Configuration/H1ECATC1/SYS/H1ECatC1.tsm. svn commit
C:/SlowControls/Target/H1ECATC1/PLC3/PLC3.pro: rebuild all, save
Copy C:/SlowControls/Target/H1ECATC1/PLC3/PLC3.pro to C:/SlowControls/TwinCAT/Source/Interferometer/Corner/Plc3.pro
C:/SlowControls/TwinCAT/Source/Current/Interferometer/Corner/Plc3.pro: Export EXP. svn commit Plc3.pro and Plc3.exp.
C:/SlowControls/Target/H1ECATC1/H1ECATC1.tsm: PLC3 rescan project; Actions -> Generate mappings, Check configuration; Save.
Copy C:/SlowControls/Target/H1ECATC1/H1ECATC1.tsm to C:/SlowControls/Scripts/Configuration/H1ECATC1/SYS/H1ECatC1.tsm. svn commit
H1ECATC1: SYS, PLC1, PLC3: 'Stop', 'Update from source', 'Compile': Compile failed.
C:/SlowControls: svn update
H1ECATC1: SYS, PLC1, PLC3: 'Stop', 'Update from source', 'Compile', 'Activate and run': TwinCAT PLC Control has stopped working
Restart computer
quit IOC
H1ECATC1: SYS, PLC1. PLC3: 'Stop', 'Update from source', 'Compile': TwinCAT PLC Control has stopped working
H1ECATC1: SYS, PLC1. PLC2. PLC3: 'Stop', 'Update from source', 'Compile': TwinCAT PLC Control has stopped working, 'Activate and run': TwinCAT PLC Control has stopped working

At this point I don't know what is going on. Going into deeper investigation...
Comments related to this report
patrick.thomas@LIGO.ORG - 13:39, Tuesday 28 October 2014 (14677)
I got the corner station back, now end X is down...'mystery errors' in IOC.
patrick.thomas@LIGO.ORG - 13:57, Tuesday 28 October 2014 (14680)
All appear to be back. Burtrestores done to 6:10 am for all PLCs for the corner station, end X and end Y.