Reports until 14:58, Friday 07 November 2014
LHO VE
kyle.ryan@LIGO.ORG - posted 14:58, Friday 07 November 2014 (14920)
Chilled water leak at booster pump in Corner Station mechanical room
Kyle, Bubba

Found the leak to be coming from the pump shaft -> Closed valve at pump inlet -> Using absorbent mats to soak up liquid (~1 gallon spill) -> Added water into chilled water system -> Will order pump replacement

The output from this booster pump supplies the Kobelco compressor, AHU3 hallway taps (no longer used) and the LVEA (no longer used) -> This chilled water branch "dead heads" (no flow) when the Kobelco compressor shuts down as the solenoid water valves close when the compressor is deenergized.