The HEPI Pumps stopped due to a level trip in the reservoir fluid height. I did a 100% scan of the system in the LVEA and found no evidence of a leak. I should have done similar in the MR but went back to my previous assumption that the fluid level declines were from the known motor drips on PS8 (1.) I had lowered the trip position to its lowest level last Tuesday so I proceeded to add fluid (Best to do while pumps are off.) Added ~2.4 gallons and then got the pump stations back running.
It seems someone else had seen a leak on the mezzinine previously--Just before leaving I noticed something (can't remember exactly what) behind the blue drum behind the reservoir, on the floor was an absorbent pad and other puddles. I first thought TCS but no it was HEPI fluid. I found a 5 second drip coming from the pipe/hose joint at the electrical break. I tightened this clamp a bit and will regularly monitor for a few days. I suspect the leak rate may have increased over time but if it had started at full rate, it would take 105 hours to leak a gallon. Since last Tuesday, I'd say the level had to drop about 3/8" or 0.3 gallons. Given the mess I cleaned up this morning, that seems about right.
So, I don't know when this leak started, it may have been much slower for a long time. Was the absorbent pad just luckily in the right spot or had someone put it there? Did someone tell me about it (a long time ago,) possibly?