Setting up DARK MICH
J. Kissel, with A. Staley (remotely again)

After fighting the IMC for quite a bit (see LHO aLOG 16005), Hugo wanted to set up a simple MICH lock in order to test his recent updates to the ISI guardians which allow for switching the ISI BS's stage 2 GS13s from high gain to low gain and back, without breaking the MICH lock (See results in LHO aLOG 16007) but I wanted to put down what needed done before I was able to restore a signal at the AS port, as it was left in an unknown & undocumented state from last night's Koji / Dan commissioning activities.

- Request ISC_DRMI guardian to DOWN. It had been left in "LOCK_DRMI_1F," which among other things, was dividing the input power by two three-five seconds after the IMC locked.
- Request ISC_DOF guardian to DOWN. This restores all globally controlled suspensions that should be to MANAGED (PRM, PR2, BS, SR2, SRM)
- Clear all DRMI WFS offsets from the M1 LOCK P and Y banks of the BS HLTS and HSTSs (which had seemingly random in size and DOF, some rather large, steering the beam who knows where)
     - Change the ramp time to something large (like 10 [sec])
     - Remember the gain value
     - Set gain to zero
     - Clear filter history
     - Restore gain
- Request MICH_DARM_LOCKED of the LSC_CONFIGS guardian.
- Clear history DC centering on for the IFO WFS
     - Open ASC overview
     - Open DC CENTERING (smallish, blue button, in the middle of the screen)
- Pull up H1:LSC-ASAIR_A_LF_OUT_256_DQ on a live dataviewer trace, and/or pull up AS port camera (sitemape > CDS > Digital Video Cameras > H1 AS Air > ! Video Control > Launch Fixed Video)
- Wait patiently while relevant optics swing into position (may take 15-30 seconds)
- Once locked (which happens reliably automatically), you need to tune the BS alignment -- but no more than 0.1 to 0.2 [urad] in either pitch or yaw. Look for 01 modes to disappear, and leave the camera dark, and the AS AIR signal (H1:LSC-ASAIR_A_LF_OUT_256_DQ) to be in the -20 to -15 region.

I've left the functional parts of the IFO in this state -- with Simple Michelson locked on a dark fringe.
Comments related to this report
alexan.staley@LIGO.ORG - 08:30, Monday 12 January 2015 (16016)

The large offset in the M1 P,Y LOCK is due to the fact that guardian has not been fully updated since the ASC loops have been modified; the guardian doesn't know to clear the history of these filters which now have an integrator. This has been on our to do list.