During ISI commissioning today the total number of channels being monitored by SDF which were changed exceeded 40. Hugh asked if I could give him the full list and the total number of changed channels.
Here is the procedure (h1isietmy is shown as an example)
On the H1ISIETMY_SDF_RESTORE.adl medm screen, in the yellow "save" section:
Set the "FILE TYPE SELECTION" to "EPICS DB AS SDF"
Ensure the the "FILE OPTIONS SELECTION" is set to "TIME NOW"
Press the Blue "SDF SAVE FILE" button, which will save the current settings as a time-stamped file (e.g. h1isietmy_sdf_150206_170209.snap)
In a terminal, type the following:
target
cd h1isietmy/h1isietmy/burt
listsdfdiffs.bsh
The output from this command is shown in the attached file