Richard, Kyle, Filiburto, Patrick, Dave
the h0vely EPICS system was modified to add the records to monitor/control the new Pirani/Cold-Cathode gauge pair connected to HAM1. HVE-LY:X0.db database file was created and added to the startup.h0vely file. The h0vely VME crate was rebooted and the new database was started. The vaccum MEDM screens were updated to show the new signals.
The H0EDCU_VE.ini file was updated and the DAQ restarted. The Pirani and Cold-Cathode calculated pressures in Torr are being recorded by the DAQ with the channel names HVE-LY:X0_100ATORR and HVE-LY:X0_100BTORR.
The vacuum overview MEDM screen which is being displayed on the CDS Web page was also updated for offsite monitoring.