james.batch@LIGO.ORG - posted 13:49, Tuesday 10 March 2015 (17177)
Awgtpman for h1asc is
The h1asc awgtpman is a special version which will allow the full 64 test points to be set.  In order to do this, the awgtpman_h1asc.cmd script (generated by RCG) was replaced with a hand-edited version which starts up awgtpman-2.9-asc-special (instead of awgtpman) and also includes a -A option to the command line.

If the h1asc model is rebuilt, this will be undone by the RCG. Coordinate model rebuilding and restarting with Jim Batch in order to ensure the modified awgtpman is running.  

This is a temporary solution to allow commissioning to continue where more testpoints are needed.  We will decide on a complete solution for the next RCG release.