Checked and set all LVEA Supply Accumulators to 70psi; Return Accumulators set to 20-30psi.
Issues found at H(am)5R(eturn), H6S(upply), H5S, H4S, B(SC)3E(ast)S,B3W(est)S,B3WR,B2N(orth)S(unable to charge due to interference), B2NR, B1NS, B1SR, H3S, H1S, H1R, H2R.
Wow, maybe easier to list the ones that did not need some gas. Most of the Supply units that needed charging where at 20psi or below. This should make a good improvement in pump pressure fluctuation coupling into to platform motion. I expect next check should see a much shorter list.