david.barker@LIGO.ORG - posted 17:53, Tuesday 17 March 2015 - last comment - 18:15, Tuesday 17 March 2015(17317)
CDS Maintenance Summary

NTP and Atomic Clock WP#5105

Dave,Jim, Vern:

The NTP server was moved in the timing rack to a lower slot. The lid to the Beckhoff chassis was reattached. The new Symmetricom Caesium Atomic Clock was racked in the location vacated by the NTP. The atomic clock was connected to UPS power and achieved sync up after 30 minutes of running.

Installation of MSR Timing Comparator

Dave, Jim:

We installed the MSR timing comparator chassis in the timing rack. We connected its timing slave fiber optics cable to the timing master (port 3) and then powered it up to +12V DC. It connected to the master with no problems

PEM CS model change WP5042

Dave, Robert:

I added the missing two narrow band radio channels to the h1pemcs model. To keep all the radio channels together on the 3rd ADC, I moved the temperature, lowfreq mic and mainsmon channels down by 2 channels in the model, and did the same with the BNC cables at the AA chassis. I checked that the low freq mic and mainsmon signals look the same in minute trends before and after the change.

OAF IPC receivers

Dave:

I removed the two IPC receivers in the h1oaf model which used to come from the LSC model but were removed. These are H1:LSC-CAL_IMC_[CTRL,F]. I grounded these channels in the h1oaf model.

DAQ restarts

Dave, Dan, Daniel, Sheila:

Several DAQ restarts were needed today: New PEM-CS model, new OAF model, new LSC model, new ASC, SUSHTTS models, new Beckhoff C1-PLC2 code, new guardian nodes.

Comments related to this report
daniel.hoak@LIGO.ORG - 18:15, Tuesday 17 March 2015 (17321)

For the ASC and HTTS models: we added IPC sender/receiver pairs to provide an ASC drive to OM3.

Also, we added the following ASC channels to the DAQ (but not to the science frames):

AS_C_PIT_OUT 2048
AS_C_SUM_OUT 2048
AS_C_YAW_OUT 2048
 
OMC_A_PIT_OUT 2048
OMC_A_SUM_OUT 2048
OMC_A_YAW_OUT 2048
 
OMC_B_PIT_OUT 2048
OMC_B_SUM_OUT 2048
OMC_B_YAW_OUT 2048
 
OMCR_A_PIT_OUT 2048
OMCR_A_SUM_OUT 2048
OMCR_A_YAW_OUT 2048
 
OMCR_B_PIT_OUT 2048
OMCR_B_SUM_OUT 2048
OMCR_B_YAW_OUT 2048