Laser Status: 
SysStat is good
Front End power is 31.8W (should be around 30 W)
FRONTEND WATCH is RED
HPO WATCH is RED

PMC:
It has been locked 5 day, 5 hr 33 minutes (should be days/weeks)
Reflected power is 2.0 Watts  and PowerSum = 24.6 Watts.
(Reflected Power should be <= 10% of PowerSum)

FSS:
It has been locked for 0 h and 1 min (should be days/weeks)
TPD[V] = 1.443V (min 0.9V)

ISS:
The diffracted power is around 9.6% (should be 5-9%)
Last saturation event was 1 d, 23 h and 6 minutes ago (should be days/weeks)