Displaying report 1-1 of 1.
Reports until 14:53, Wednesday 22 April 2015
LHO VE
kyle.ryan@LIGO.ORG - posted 14:53, Wednesday 22 April 2015 (18012)
Adjusted step voltage current setpoints for 3 of 6 IP controllers at the Corner Station
CS pressure ~1 x 10-8 torr which is just below values programmed to step to 5000V -> Adjusted step set points from 1.5 x 10-4 amps to 3.0 x 10-4 amps for 3 of the 6 IP controllers at the Corner Station -> will continue optimal tweaking over the next few days