H1 CDS
patrick.thomas@LIGO.ORG - posted 12:52, Tuesday 28 April 2015 (18099)
restarted Beckhoff computer at end X
Biweekly crash recovery

Logged in. Closed system manager. Said no to save current changes. Restarted computer. Errors in EPICS IOC. Closed EPICS IOC.
Restarted computer again to get screenshot of errors in EPICS IOC (see attached).

Closed EPICS IOC.

Opened LIGO TwinCAT Target Configuration GUI
Selected H1ECATX1 -> SYS, PLC1, PLC2, PLC3.
Clicked Stop. Clicked Update from source. Clicked Compile. Failed (see attached)
Ran svn update on C:SlowControls. No changes at end X. (see attached)
Ran svn st on C:SlowControls. No local modifications.

Opened LIGO TwinCAT Target Configuration GUI
Selected H1ECATX1 -> SYS, PLC1, PLC2, PLC3.
Clicked Stop. Clicked Update from source. Clicked compile. This time it completed successfully. Clicked Activate and run.
Got message: No boot project created since last download. Exit anyway? Clicked OK. Said it completed successfully.
Clicked Restart EPICS database.
PLC1 and PLC3 came back. PLC2 did not (see attached) Why is the location Corner?

Opened PLC2 from target. Logged in and selected run. PLC2 came back.

Went to /ligo/cds/lho/h1/burt/2015/04/28/00:10
Ran:
burtwb -f h1ecatx1plc1epics.snap
burtwb -f h1ecatx1plc2epics.snap
burtwb -f h1ecatx1plc3epics.snap
Images attached to this report