Kyle, Gerardo Today we wanted to quantify the gas load "contribution" of the known leaking all-metal 2.5" Vent/Purge valve at the X-end station. SETUP X-end open to BT (GV19, GV20 open) Main Turbo backed only by the leak detector (no parallel pumping) RESULTS LD helium baseline < 10-10 torr*L/sec before valving turbo into X-end volume Helium background signal = 3 x 10-8 torr*L/sec after valving turbo into X-end volume Valved-out IP12 Removed NW50 blank from closed Vent/Purge 2.5" all-metal valve (i.e. vented air side of closed metal valve) X-end pressure responded by rising to low 10-7 torr Sprayed audible flow of helium on air side of closed valve while monitoring helium signal Helium signal rose rapidly then leveled-off and peaked at 2 x 10-5 torr*L/sec (signal peaked after ~10 seconds of spraying but I continued spraying until ~30 seconds) Spent the next few hours pumping system with the turbo pump to remove introduced helium. We also added an O-ring valve in series with the leaking valve and evacuated the air side of this valve CONCLUSION Traditionally we have only used the vendor supplied hand knobs to open/close these Vent/Purge 2.5" metal valves (1 per isolate-able volume). The allowable torque specs far exceed what can be applied using these knobs. As such, our valves are likely under-torqued as a rule and, as was demonstrated yesterday, this leak could likely be eliminated by tighing this valve using a wrench. As this particular valve has a "gappy" conflat joint on the vacuum side, we didn't want to "fix" it using a wrench (long lever) while we are open to the BT and while commissioning time is at a premium. The main take away is that all of our poor pressure level at the X-end can be attributed to this under-torqued metal valve and that we have no reason to suspect GV19 or GV20.