I reviewed front end code which have outstanding local mods. I committed to SVN h1alsex.mdl, h1alsey.mdl, h1iopsusauxex.mdl, h1iopsusauxey.mdl, h1iopsusex.mdl, h1iopsusey.mdl. Files which still need committing: ASCIMC_MASTER.mdl, lscimc.mdl and CD_STATE_MACHINE.c
I "greened" up the IOP SDF by switching the DAC Duotone OFF on h1lsc, h1iscex, h1iscey.
I ensured filtermodule file synchronisation by pressing the LOAD_COEFF buttons on all models.
I verified all safe.snap files in the target areas are symbolic links to userapps, and checked in local mods.
I'm in the process of ensuring all filter module files are symbolic links to userapps (12 were not) and checking these into SVN. COEFF_LOAD is needed when the file is changed from local to symbolic link to clear the "modified file" message.
I copied the latest Beckhoff DAQ INI files to the DAQ. I had to remove the duplication of the H1:PSL channels as was seen before. The DAQ was restarted after this morning's model changes.
The IRIG-B excursion of h1seih45 following its power supply swap took several hours to come back down. The CDS Overview is now GREEN, any non-GREENs should be investigated.