Got alarm on CS RO system. Bubba talked me through a system reset. CS RO system is back up and running. To Reset RO System: 1). The RO system is located in the "water room", (through door to the right) in the Carpenter's shop 2). The RO Panel (OSMO 23G) is to the left just inside the door to the water room 3). Press the "mute" button to silence the alarm 4). Press the "Off" button to shutdown the RO system 5). Press the "On" button to restart the RO system 6). When the RO transfer pump starts - the pressure gauge should be reading around 58psi The RO transfer pump is a red vertical pump on the floor half way down the back wall.