Reports until 13:13, Tuesday 02 June 2015
H1 CDS (CDS)
david.barker@LIGO.ORG - posted 13:13, Tuesday 02 June 2015 - last comment - 15:03, Tuesday 02 June 2015(18789)
front end filter module files all cleanly loaded

Several front ends had partially loaded filter modules. To prepare H1 for ER7 data taking, I ran a script which pressed all LOAD_NEW_COEFF buttons on every model. I'll periodically "load all filters" if we encounter any partially loaded files during ER7.

Comments related to this report
david.barker@LIGO.ORG - 15:03, Tuesday 02 June 2015 (18794)

after doing this I noticed that three filters in the LSC were being regularly reloaded. Evan tracked this down to the ALIGN_IFO.py guardian which was incorrectly writing a 1 to the RSET PV rather than 2 (load coefficients rather than clear history). This was fixed.