Reports until 17:33, Friday 05 June 2015
H1 CDS
david.barker@LIGO.ORG - posted 17:33, Friday 05 June 2015 (18917)
CDS overview MEDMs changed to show stuck DAQs

WP5250

I have changed the CDS STATE_WORD overview MEDM screens to show a red rectangle if any of the DAQ systems stop updating. If today's freeze up of the broadcaster were to re-occur, it should now show a red alert. I'm using the h1ioppsl0 GPS counter as the standard against which I compare the DAQ GPS counters. If they lag by 60 seconds the alert is shown.