Reports until 15:51, Tuesday 23 June 2015
H1 General
cheryl.vorvick@LIGO.ORG - posted 15:51, Tuesday 23 June 2015 (19297)
fmcs alarm updated

I updated the fmcs alarm config file to put the RO Water system in it's own catagory, so it's easier to see, and easier to differentiate RO Water from alarms that are truely CRITICAL the moment they trigger.

New RO_WATER Guidance:

            $GUIDANCE

             Reverse Osmosis Water System is in alarm.

             The site may have potable water for 

             a while, but eventually will run out.

             Call John or Bubba

             $END

 

Channels removed per John's OK:

 

CHANNEL  CRITICAL H0:FMC-MY_CY_H2O_SUP_DEGF

              $ALARMCOUNTFILTER 300 300

CHANNEL  CRITICAL H0:FMC-MY_CY_H2O_RET_DEGF

              $ALARMCOUNTFILTER 300 300

CHANNEL  CRITICAL H0:FMC-MX_CY_H2O_SUP_DEGF

              $ALARMCOUNTFILTER 300 300

CHANNEL  CRITICAL H0:FMC-MX_CY_H2O_RET_DEGF

              $ALARMCOUNTFILTER 300 300

 

No longer CRITCAL alarms, and do not need to be in the fmcs alarm handler.