Displaying report 1-1 of 1.
Reports until 18:17, Wednesday 24 June 2015
H1 CDS
david.barker@LIGO.ORG - posted 18:17, Wednesday 24 June 2015 (19314)
h1ascimc.mdl file changed to fix compiling error

Sheila, Kiwamu, Jim, Dave:

It appears that following the last successful build of h1ascimc on April 21 of this year, the file was modified to use a fastPZT version of the common ASCIMC_MASTER part. This part was not found, and the model would not compile. For now I have modified h1ascimc.mdl to use the standard ASCIMC_MASTER/ASCIMC part. The common part's input ports aligned correctly, but I had to manually connect the output ports up in the order found. Someone should verify that the DAC channels are correct, they are (counting from 0 through 15)

ch08 = PZT_P_OUT

ch09 = PZT_YAW_OUT

ch10 = SPAREOUT2

ch11 = MCREFL-SHUTTER_OPEN

The output IPC parts are labeled so I'm confident  they are connected correctly.

I have not installed this model, it needs checking before we do this.

Displaying report 1-1 of 1.