Reports until 18:11, Friday 17 July 2015
H1 CDS (DAQ)
david.barker@LIGO.ORG - posted 18:11, Friday 17 July 2015 (19724)
h1suetmypi model started

A new H1 model was started this afternoon on h1susey. It is h1susetmypi, which is a copy of the L1 model minus the IPC input receievers and the DAC outputs on the top level. The new model has DCU_ID=127 and runs at 64kHz.

The initial startup failed with a "DAQ too small" error. We boosted the DQ channels from 2kHz to 64kHz (commissioning frame only) and added some EpicsIn parts at the top level to get through this error. We will investigate this further next week.

The new model was added to the DAQ and the DAQ was restarted. I have added it to the CDS ENG overview MEDM screen, I'll add it to the rest later.