Reports until 02:24, Wednesday 29 July 2015
H1 ISC
matthew.evans@LIGO.ORG - posted 02:24, Wednesday 29 July 2015 (20019)
OM dithers reduced

The OM dither lines (around 1.7kHz) are not being used, so I turned them down by a factor of 10.

H1:OMC-ASC_P1_CLOCK_GAIN = 0.1

I'll leave them on to make sure that we don't run into DAC bit-noise problems (e.g., no HF signal gathers the DAC noise around DC, which is not fun).

Images attached to this report