Looking at timeseries graphs for photodiaodes from two separate locks (7-28-15 8:00:00 UTC for two hours AND 8-1-15 10:15:00 UTC for two hours) I've tightened up all the saturation thresholds in the LSC ODC.
| Channels | New Threshholds |
| POP_A_RF9 | 21000 |
| POPAIR_A_RF9 | 27000 |
| POP_A_RF45 | 5000 |
| POPAIR_A_RF45 | 5000 |
| REFL_A_RF9 | 4000 |
| REFLAIR_A_RF9 | 300 |
| REFL_A_RF45 | 4000 |
| REFLAIR_A_RF45 | 350 |
| REFAIR_B_RF27 | 3500 |
| REFLAIR_B_RF135 | 350 |
| ASAIR_A_RF45 | 4500 |
Updated SDF to reflect these new changes so they will not get lost in future reboots.