Dust Monitor Alarm Levels

   Reset the dust monitor alarm levels for the LVEA, VEAs, and PSL from the tighter levels associated with the June vents to the levels for the O1 environment. The current values are:

Room Air Size Minor Alarm Major Alarm
LVEA & VEAs Clean-10000
  0.3-Microns 14,000 20,000
  0.5-Microns 7,000 10,000

 

Anti & Laser Room Size Minor Alarm Major Alarm
PSL Enclosure Clean-1000
  0.3-Microns 1,400 2,000
  0.5-Microns 700 1,000

The Diode Room and Optics Lab alarm levels will be adjusted when I can get confirmation of their particle level requirements

Comments related to this report
jeffrey.bartlett@LIGO.ORG - 14:30, Wednesday 12 August 2015 (20485)

Set the Diode Room alarms to the same Clean-1000 levels as the PSL.