Reset the dust monitor alarm levels for the LVEA, VEAs, and PSL from the tighter levels associated with the June vents to the levels for the O1 environment. The current values are:
| Room Air | Size | Minor Alarm | Major Alarm |
|---|---|---|---|
| 0.3-Microns | 14,000 | 20,000 | |
| 0.5-Microns | 7,000 | 10,000 |
| Anti & Laser Room | Size | Minor Alarm | Major Alarm |
|---|---|---|---|
| 0.3-Microns | 1,400 | 2,000 | |
| 0.5-Microns | 700 | 1,000 |
The Diode Room and Optics Lab alarm levels will be adjusted when I can get confirmation of their particle level requirements
Set the Diode Room alarms to the same Clean-1000 levels as the PSL.