Faulty compressor
Late last week we had one of the two compressors quit on the AAON unit at the staging building. See FRS 3455. This unit is designed to supplement the original 12 T Carrier chiller which also has one of the two condenser fan motors beginning to show signs of failure. See FRS 3451.

The failed compressor has been disconnected and the AAON is operating at 50% capacity which should be enough to assist the main unit enough to keep the staging building cool especially during the somewhat cooler temperatures.

The faulty parts have now been ordered and hopefully arrive before any additional triple digit temperatures.

 