Reports until 17:21, Wednesday 02 September 2015
H1 General
cheryl.vorvick@LIGO.ORG - posted 17:21, Wednesday 02 September 2015 (21158)
FMCS alarm Major/Low: H0:FMC-EX_CY_H2OSUP_DEGF

Confirmed with a trend that the ambient temperatures have pushed the EX chiller into and past the low alarm levels.

The Major/Low alarm at 23:42UTC had a temperature of 34.99F.

The channel went back in the NO_ALARM state at 23:47UTC with a temperature reading of 35.45F.

I followed the alarm handler guidance and made a 10 day trend which shows that this has been happening for a while, so no notification/action needed.