Reports until 08:28, Saturday 21 November 2015
LHO FMCS
john.worden@LIGO.ORG - posted 08:28, Saturday 21 November 2015 - last comment - 10:45, Saturday 21 November 2015(23622)
Heaters incremented.

I talked with Jeff and Travis and we decided to increment heat as we are running out of range in the FMCS controls. Outdoor temps have fallen to ~18F overnight.

In the LVEA - incremented HC1B from 9 to 10 ma (control signal) at 8:16 PST

EX - incremented HC3 from 10-11 ma at 8:18

EY - incremented HC3 from 10-11 ma at 8:19.

 

Edit - incremented EX HC3 from 11- 12ma at 8:33 for some additional heat as response was not sufficient.

Comments related to this report
betsy.weaver@LIGO.ORG - 10:39, Saturday 21 November 2015 (23624)

Attached are plots of the ETMs moving in verticalwith the temperature swing. 

Images attached to this comment
betsy.weaver@LIGO.ORG - 10:45, Saturday 21 November 2015 (23625)

And the corner station BS and ITM suses...