0005 - 0105 hrs. local -> Back and forth to X2-8 to refuel diesel generator
Added ~ 5 gallons of fuel to generator -> found blown fuse for 1 of 2 variacs supplying heat to 1 1/2" tubes + gate of 10" gate valve -> replaced 5A fuse -> OK now -> T/C for ion pump indicates 188C -> adjusted output (decreased) for both variacs supplying heat to ion pump (150C is target)