Displaying report 1-1 of 1.
Reports until 03:35, Friday 27 November 2015
H1 General
edmond.merilh@LIGO.ORG - posted 03:35, Friday 27 November 2015 - last comment - 06:44, Friday 27 November 2015(23753)
Critical Air Handler Alarm

Critical Alarm at 11:15 for H0:FMC-CS_LVEA_REHEAT_2B_DEGF. Attached trend show past 24 hours for this channel. I'm not entirely sure how long this alarm has been present. Also attached is a screenshot of the current CS FMCS. I noticed the aLog regarding the temp increase at Y end . I have not yet found one regarding the corner station.

Images attached to this report
Comments related to this report
john.worden@LIGO.ORG - 06:44, Friday 27 November 2015 (23756)

Thanks Ed,

Bubba and I are aware of these alarms and are working on the issue. These should probably not be flagged as "critical" as they are duct heater temperatures and a temperature of 100F is not unusual for these.

Our reduced fan flow rates are contributing to the increased temperatures in the ducts.

 

 

Displaying report 1-1 of 1.