LVEA Temperature control

I noticed that the LVEA temperature control was running out of range so I have added an additional stage of heat.

HC1A control has been set to 15ma (was 4 ma) It appears that the first stage heater is not working so this should turn on the second stage.

The duct temperature is behaving normally - first plot. Second plot shows the face bypass dampers railing at 7ma.