Reports until 15:34, Friday 06 April 2012
LHO VE
kyle.ryan@LIGO.ORG - posted 15:34, Friday 06 April 2012 (2559)
Y-mid leak testing ended
Found 10-5 torr*L/sec leak(s) at NW40 joint(s) at the exhaust of the MTP.  This size of leak(s) ~10ft away from the the application of helium at the new CF joints was causing some confusing results -> Tightened NW40 clamps (they were nearly falling off!) and OK now

Kyle, Gerardo 
Valved-in IP9*Valved-out MTP*Dumped GV10 and GV11 gate annulus volumes into aux. pump carts*Opened GV10 and GV11