h1conlog1-master has still not connected to 1736 channels since the maintenance work yesterday (alog 26112). I checked the unmonitored channel list and with the exception of two, they are all of the channels that are not read-only in /opt/rtcds/lho/h1/target/h1ecatc1/h1ecatc1plc1epics/autoBurt.req, that is h1ecatc1 PLC1. The two other channels are H1:PEM-CS_DUST_LAB1_ENABLE and H1:PEM-CS_DUST_LAB2_ENABLE, which I confirmed do not respond to a caget. I can do a caget from h1conlog1-master on the couple of unmonitored channels on h1ecatc1 PLC1 that I tried. It is also worth noting that conlog-test-master has the same issue with the same channels. I tried restarting conlog-test-master and it still does not connect to these channels.