gerardo.moreno@LIGO.ORG - posted 16:55, Friday 18 March 2016 (26146)
Power Loss of Y-End Station Instrument Air Compressor

Richard M, Filiberto C, Peter K, Ed M, Gerardo M.

Lost power to the Y-End station Instrument air compressor.

Initial inspection revealed the circuit breaker had tripped.

Found main lead wires shorted against a stud.

Wires were replaced and power restored to Y-End station Instrument air compressor.

CP7 went into alarm due to the lack of air, but is now recuperating, it reached a low of 81.3% full, as of now is at 86.2% and green.