Displaying report 1-1 of 1.
Reports until 19:16, Thursday 24 March 2016
H1 TCS (GRD)
nutsinee.kijbunchoo@LIGO.ORG - posted 19:16, Thursday 24 March 2016 (26243)
Added HWS test items to DIAG_MAIN

Kiwamu, Nutsinee

------------------------------------------------------------------------------------------------------------------------------

Code added to line 115 - line 136

First test checks if the number of "peaks" measured by the HWS code makes sense. If below 800 -- not enough return SLED beam. If above 4096 (12 bit), something's wrong.

Second test checks if HWS code time stamp is correct compared to the actual GPS time. If |dt| > 15 seconds then the code must have stopped running.

------------------------------------------------------------------------------------------------------------------------------

@SYSDIAG.register_test
def TCS_HWS():
    #Make sure # of pixels are good
    pkcnts_X = ezca['TCS-ITMX_HWS_TOP100_PV']
    pkcnts_Y = ezca['TCS-ITMY_HWS_TOP100_PV']
    #If below 800 -- not enough return SLED light
    #If above 4096 -- above theoretical number (12 bit) -- something's wrong
    if not (pkcnts_X > 800) and (pkcnts_X < 4096):
       yield "HWSX Peak Counts BAD!!"
    if not (pkcnts_Y > 800) and (pkcnts_Y < 4096):
       yield "HWSY Peak Counts BAD!!"
    #Check if HWS GPS time agrees with current GPS time
    a = subprocess.Popen(['tconvert','now'], stdout = subprocess.PIPE)
    gpstime, err = a.communicate()
    gpsfloat = float(gpstime.strip(' '))
    #Fetch HWS GPS time
    liveGPS_X = ezca['TCS-ITMX_HWS_LIVE_ACQUISITION_GPSTIME']
    liveGPS_Y = ezca['TCS-ITMY_HWS_LIVE_ACQUISITION_GPSTIME']
    if np.abs(gpsfloat - liveGPS_X) > 15 :
    yield "HWSX Code Stopped Running"
    if np.abs(gpsfloat - liveGPS_Y) > 15:
    yield "HWSY Code Stopped Running"
 

Displaying report 1-1 of 1.