With the need for heat in the LVEA low we took Heater 5 offline to convert it over to the variac system. To protect the components we have limited the unit to 440V AC. Must have a bad heater on C phase as the current draw was too low. I have to talk to the vendor about adjusting the span on the controller. We now max out at 14ma instead of 20ma. 4ma off <.5A 6ma 2.41 A 90V 8ma 8.6 A 175V 10ma 19.1A 265V 12ma 33.5A 355V 14ma 50.1 A 439V