Reports until 14:15, Friday 29 April 2016
LHO VE
chandra.romel@LIGO.ORG - posted 14:15, Friday 29 April 2016 (26884)
CP3 overfill
MidY @ 1:40pm local

Opened CP3 bypass LLCV 1/2 turn with bypass exhaust valve open. Took 8:49 min. until vapor/liquid started to flow out the exhaust pipes. I waited several minutes before closing the bypass exhaust valve. Closed it a few times, pressure sounded high, so I opened it back up and then several seconds later liquid started to pour out. I did this three times, and then waited many minutes before finally leaving bypass exhaust valve closed.