I am adjusting the CP2 LLCV PID parameters controlled by Beckhoff system. 1. Set to manual mode at 35% open and adjust PI settings while in manual mode and observe value in data viewer real time. PI still updates its values in manual mode. Note that every time a PID value is changes the LLCV % open value resets. The pneumatic actuator is physically jouncing up and down and will wear out prematurely at current Beckhoff settings. The new electronic actuator on CP1 is not jolting as much as CP2, but up/down movement is still noticeable at rapid rate - PID parameters should be addressed. Have not surveyed the other five actuators (CP3 doesn't count).