chandra.romel@LIGO.ORG - posted 14:20, Friday 13 May 2016 - last comment - 17:49, Friday 13 May 2016(27182)
CP 5 & 6 PIDs
Richard changed PID settings on CP 5 & 6 today. Current settings:

CP5
Gain: 7
Integral: 460
Set Pt: 90

CP6
Gain: 6
Integral: 360
Set Pt: 88

Set points are set lower than nominal 92% so PID experiments can continue Monday.
Comments related to this report
chandra.romel@LIGO.ORG - 17:49, Friday 13 May 2016 (27186)
Liquid levels of CP 5 & 6 have settled to the set points.
Images attached to this comment