Displaying report 1-1 of 1.
Reports until 21:27, Monday 06 June 2016
LHO VE
chandra.romel@LIGO.ORG - posted 21:27, Monday 06 June 2016 - last comment - 06:59, Tuesday 07 June 2016(27596)
GV7 sagged
GV7 has sagged since John and I reinstated normal operational state this morning by re-applying 50-60 psi pressure upward on piston and removing locking pin. Not sure how far down it has sagged. I suggest waiting to run laser until it's boosted back up Tuesday morning by someone from the vacuum group.
Comments related to this report
kyle.ryan@LIGO.ORG - 21:33, Monday 06 June 2016 (27597)
I'll fix tonight and come in an hour later in the morning
kyle.ryan@LIGO.ORG - 22:30, Monday 06 June 2016 (27599)
3 hour trend of CS instrument air range between 62 psi - 82 psi.  

As found, 55 psi < GV5, GV6, GV8 < 60 psi, GV7 = 38 psi -> Adjusted all for > 60 psi. 

Note: the LVEA was quiet and I could easily hear the displaced air exiting the pneumatic manifold vent port.  I would guess that the gate had sagged several inches (foot?) based upon duration of audible venting and the convincing "THUNK" of it hitting the hard stops.  

chandra.romel@LIGO.ORG - 06:59, Tuesday 07 June 2016 (27602)
Thank you, Kyle!
Displaying report 1-1 of 1.