The following RFM senders (library part cdsIPCx_RFM) are now in h2iscey:
H2:ISCEY-SUSTMSY_PIT H2:ISCEY-SUSTMSY_YAW H2:ISCEY-SUSETMY_LONG H2:ISCEY-SUSETMY_PIT H2:ISCEY-SUSETMY_YAW
I have also added the corresponding receivers to h2sustmsy and h2susetmy.
All models have been recompiled, installed, and restarted. I have tested the connections, by applying offsets to the filter modules that output to the senders, and the connections seem to be working fine.
I have left the outputs and inputs to the filter modules that connect to the RFM senders and receivers off for now. The input to the H2:ISCEY-SUSETMY_LONG sender is just a constant at the moment (value = 666), since there is no control signal for that output yet. That will likely be added today.
I note, since I forgot, the receivers need to have their inputs grounded to indicate they are receivers. Otherwise the model will fail to compile. Similarly, you can not ground the input on a sender or it will be interpreted by the RCG as a sender. If the input to the receiver needs to be set to a specific value the Simulink "constant" part can be used.